XHHW-2
Applications
Type XHHW-2 conductors are primarily used in conduit or other recognized raceways for services, feeders, and branch circuit wiring, as specified in the National Electrical Code®. Type XHHW-2 conductors may be used in wet or dry locations at temperatures not to exceed 90°C. Voltage rating for XHHW-2 conductors is 600 volts.
Specifications
Type XHHW-2 conductors meet or exceed all applicable ASTM Specifications, UL Standard 44, Federal Specification A-A-59544, NEMA WC 70 (ICEA S-95-658) and requirements of the National Electrical Code® (NFPA 70).
Construction
Type XHHW-2 copper conductors are annealed (soft) copper. Insulation is an abrasion, moisture, and heat resistant cross-linked polyethylene (XLP). Conductor sizes 2 AWG and larger listed and marked sunlight resistant in black only. Conductor sizes 1/0 AWG and larger listed and marked for Cable Tray Use.
Product Chart
Recommended Sample Specifications
Conductors shall be UL-listed Type XHHW-2, suitable for operation at 600 volts or less in wet or dry locations, at temperatures not to exceed 90°C. Conductors shall be annealed copper.